Bridge-Type SFCL Utilization to Improve the Microgrid Transient Stability and Economic Feasibility

  • Roy Bayu Negara Universitas Gadjah Mada
  • Fransisco Danang Wijaya Universitas Gadjah Mada
  • Lesnanto Multa Putranto Universitas Gadjah Mada
  • Mohd. Brado Frasetyo Universitas Gadjah Mada
Keywords: Microgrid, Fault, Current Limiter, Renewable Energy, Transient, Bridge-Type SFCL, Economic Feasibility

Abstract

Currently, renewable energy (RE) generators are widely used by society to reduce emissions. Therefore, a RE-sourced microgrid system coexisting with conventional energy is being developed. However, these electrical energy systems experience transient disturbances such as short circuits, load increase, and decrease in generator output. These disturbances can result in voltage drops and frequency instability. Therefore, efforts are needed to maintain system stability by using a superconducting fault current limiter (SFCL). The SCFL selection is based on its capability to limit the fault current and its speed in providing protection during transient disturbances. The utilized SFCL model is the bridge-type SFCL with two inductors as its main components. Under normal conditions, the current flows through two inductors, and when a fault occurs, the current will go through one inductor. This research was conducted in a scenario where a fault occurred. The voltage value without a bridge-type SFCL during the fault condition was 2.5 V. When a bridge-type SFCL was used, the voltage value was 207 V. Without a bridge-type SFCL, the measured current was 30 kA, whereas the measured current was 1.1 kA with one. The frequency range was 49.7 Hz - 50.2 Hz without bridge-type SFCL and 49.9 Hz - 50.1 Hz with bridge-type SFCL. This research also added an economic feasibility calculation to determine the microgrid system feasibility when using bridge-type SFCL. The calculation consisted of four parts, i.e., net present value (NPV), profitability index (PI), discounted payback period (DPP), and internal rate of return (IRR). Economic feasibility was obtained for an NPV value of US$6,865,405, a PI value of 2.4, a DPP value of four years, and an IRR value of 28.59%. When the obtained value is compared to the feasibility standard, it is determined that a microgrid with SFCL is feasible.

References

“Diseminasi RUPTL 2021-2030,” PT PLN (Persero), 2021.

Y. Sawle, S.C. Gupta, and A.K. Bohre, “Review of Hybrid Renewable Energy Systems with Comparative Analysis of Off-Grid Hybrid System,” Renew. Sustain. Energy Rev., Vol. 81, pp. 2217–2235, Jan. 2018, doi: 10.1016/j.rser.2017.06.033.

“Rencana Usaha Penyediaan Tenaga Listrik (RUPTL) PT PLN (Persero) 2021-2030,” PT. PLN (Persero), 2021.

Y.A. Medvedkina and A.V. Khodochenko, “Renewable Energy and Their Impact on Environmental Pollution in the Context of Globalization,” 2020 Int. Multi-Conf. Ind. Eng., Mod. Technol. (FarEastCon), 2020, pp. 1–4, doi: 10.1109/FarEastCon50210.2020.9271508.

M. Ahmed, L. Meegahapola, A. Vahidnia, and M. Datta, “Stability and Control Aspects of Microgrid Architectures-A Comprehensive Review,” IEEE Access, Vol. 8, pp. 144730–144766, Aug. 2020, doi: 10.1109/ACCESS.2020.3014977.

L. Sun, X. Zhao, and Y. Lv, “Stability Analysis and Performance Improvement of Power Sharing Control in Islanded Microgrids,” IEEE Trans. Smart Grid, Vol. 13, No. 6, pp. 4665–4676, Nov. 2022, doi: 10.1109/TSG.2022.3178593.

L. Chen et al., “Application of a Resistive Type Superconducting Fault Current Limiter for a DC Microgrid System,” 2018 IEEE Int. Conf. Appl. Supercond., Electromagn. Devices (ASEMD), 2018, pp. 1–2, doi: 10.1109/ASEMD.2018.855893.

M.S. Alam et al., “An Efficient Protection and Control Schemes for IBDG System with Resistive Superconducting Current Limiter,” 2021 5th Int. Conf. Elect. Eng., Inf. Commun. Technol. (ICEEICT), 2021, pp. 1–5, doi: 10.1109/ICEEICT53905.2021.9667917.

M.S. Alam et al., “An Efficient Adjustable Duty Control Based Current Limiter for Grid-Connected Solar PV System,” 2021 5th Int. Conf. Elect. Eng., Inf. Commun. Technol. (ICEEICT), 2021, pp. 1–5, doi: 10.1109/ICEEICT53905.2021.9667899.

L. Chen et al., “Application and Design of a Resistive-Type Superconducting Fault Current Limiter for Efficient Protection of a DC Microgrid,” IEEE Trans. Appl. Supercond., Vol. 29, No. 2, pp. 1–7, Mar. 2019, doi: 10.1109/TASC.2018.2882228.

M. Chewale et al., “A Comprehensive Review on Fault Current Limiter for Power Network,” 2019 Int. Conf. Recent Adv. Energy-Efficient Comput., Commun. (ICRAECC), 2019, pp. 1–7, doi: 10.1109/ICRAECC43874.2019.8995098.

I.K. Okakwu, P.E. Orukpe, and E.A. Ogujor, “Application of Superconducting Fault Current Limiter (SFCL) in Power Systems: A Review,” Eur. J. Eng. Res., Sci., Vol. 3, No. 7, pp. 28–32, Jul. 2018, doi: 10.24018/ejeng.2018.3.7.799.

J. Xu, X. Cao, and Z. Hao, “A Droop Control Strategy Based on Synchronous Rectifier to Modulate the Frequency and Voltage in AC Microgrid,” 2019 22nd Int. Conf. Elect. Mach., Syst. (ICEMS), 2019, pp. 1–5, doi: 10.1109/ICEMS.2019.8921702.

S. Ullah, L. Khan, I. Sami, and J.-S. Ro, “Voltage/Frequency Regulation with Optimal Load Dispatch in Microgrids Using SMC Based Distributed Cooperative Control,” IEEE Access, Vol. 10, pp. 64873–64889, Jun. 2022, doi: 10.1109/ACCESS.2022.3183635.

R. Tan, Y. Wang, and S. Zhang, “Coordination Scheme of SFCL and SMES in the DC Microgrid for Fault Current Limiting and Voltage Stability,” 2020 IEEE Int. Conf. Appl. Supercond., Electromagn. Devices (ASEMD), 2020, pp. 1–2, doi: 10.1109/ASEMD49065.2020.9276114.

I. Boldea, “Electric Generators and Motors: An Overview,” CES Trans. Elect. Mach., Syst., Vol. 1, No. 1, pp. 3–14, Mar. 2017, doi: 10.23919/TEMS.2017.7911104.

M. Satish and H.S. Veena, “Transient Stability Enhancement of a Microgrid Consisting of Solar PV and DFIG based Wind Turbine System Using Bridge Type SFCL,” 2020 Int. Conf. Smart Technol. Comput. Elect., Electron. (ICSTCEE), 2020, pp. 408–411, doi: 10.1109/ICSTCEE49637.2020.9277174.

Badan Pusat Statistik Kabupaten Ketapang, “Rata-Rata Kecepatan Angin Kabupaten Ketapang (Knot), 2018-2019,” 2020, [Online], https://ketapangkab.bps.go.id/indicator/151/123/1/rata-rata-kecepatan-angin-kabupaten-ketapang.html

“Aturan Jaringan Sistem Tenaga Listrik (Grid Code),” Regulation of the Minister of Energy and Mineral Resources of the Republic of Indonesia, No. 2, 2020.

“Standar-Standar Tegangan,” PT PLN (Persero), 1995.

Published
2023-05-31
How to Cite
Roy Bayu Negara, Fransisco Danang Wijaya, Lesnanto Multa Putranto, & Mohd. Brado Frasetyo. (2023). Bridge-Type SFCL Utilization to Improve the Microgrid Transient Stability and Economic Feasibility. Jurnal Nasional Teknik Elektro Dan Teknologi Informasi, 12(2), 144-150. https://doi.org/10.22146/jnteti.v12i2.4679
Section
Articles